Comparison of DOL and Sure-Start 6

These oscillograms show the starting current waveforms.

No load voltage: 254 volts rms

These waveforms show the effect of the motor start current on the voltage at the condenser unit terminals.

The same waveforms but stretched and showing the voltage.

 

Start current of 143 Amps rms

254 volts falling to 213 volts rms

 

Start current of 42.7 Amps rms

254 volts falling to 245 volts rms

Motor: Danfoss HLM068T5LP6 4.4kw Single Phase                                        

4/14 Ralph Black Drive

Wollongong 2500

NSW Australia

To contact us:

Phone: +61 2 4229 2069

Fax: +61 2 4229 2069

E-mail:john@hypereng.com

 

                 HYPER ENGINEERING is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information herein is intended only for use by persons having the appropriate technical knowledge and skills, at their own discretion and risk. Since conditions of use are outside of HYPER ENGINEERING’S control we cannot assume any liability for results obtained or damages occurred due to improper application.