HYPER ENGINEERING is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information herein is intended only for use by persons having the appropriate technical knowledge and skills, at their own discretion and risk. Since conditions of use are outside of HYPER ENGINEERING’S control we cannot assume any liability for results obtained or damages occurred due to improper application. |
|
Sure-Start 6 |
|
This product has been developed specifically to soft-start large single phase compressors and motors. It provides a dramatic reduction in the starting current but still provides full start torque. It will automatically adjust itself to cover the range 3 to 6Hp. It is fully self contained in a conveniently small double insulated enclosure. Two versions are available, a “slave” which is used in conjunction with a contactor, and a “master” which includes the function of the contactor.
Features · For motors up to 6Hp electrical · Limitation of starting current to less than 45 Amps · A substantial reduction in light flicker. · Self adjusting to motor current - no manual adjustment or calibration necessary · Many motor protection functions: - Low voltage shutdown - Locked rotor recognition and shutdown - Delay function to limit number of motor starts per hour · Thyristor protected contactor for long life (only in the · master model) · No extra motor contactor needed (only in the master model) · Internal timing prevents rapid cycling faults · Useful for non-grid application · Self diagnostics · Easy Installation– Can be supplied with an optional wiring harness.
|

|
150 Amps |
|
40 Amps |
|
45 Amp Compliance Even for 6Hp compressors Engineered for air-conditioning but suitable for all PSC motors
|
|
Current |
|
Before After 6Hp 150A 40A 5Hp 130A 36A 4Hp 100A 29A 3Hp 75A 23A 2Hp 50A 15A |




|
Voltage Frequency Maximum Starting Current Maximum Step Starting Current Maximum Supply Impedance Control Input Dimensions Material IP Rating Software Cycle Delay Software Fault Delay Software Optimization Duty Cycle Shutdown on Low Voltage Power Loss Reset Motor Monitoring Motor Reversal EMC Compliance # |
|
220-240 volts AC Models for 50Hz or 60Hz 44 amps rms, typically 40amps rms 39 amp rms, typically 36amps rms 0.8ohms 240 volts AC 13mm x 75mm x 50mm high ABS Flameproof. UL-94VO IP217 (IP547 on request) 180 seconds. Defrost Cycle Compatible 300 seconds 2.5Hp to 6Hp compressors 15 starts / hour Less then 195 volts 100mS detection Monitors start winding potential Shutdown for 180 seconds N2002
|
|
Sure-Start 6 Specifications |
|